CBecause of industry’s growing need to comply with NFPA and Factory Mutual requirements, more than 60% of White Systems vertical carousels are sold with built-in fire suppression systems. |
|||||||||||
|
|
![]()
White Systems vertical carousels can be fitted with wet-pipe sprinkler systems, single-interlock preaction sprinkler systems, or clean agent gaseous suppression systems.
Generally, sprinkler systems are used to confine a fire and protect a structure. They are the most cost effective fire suppression system. Two types are available, wet-pipe and preaction systems.
Preaction systems feature air pressurized sprinkler pipes isolated from the supply water by a preaction valve. A heat or smoke detection system opens the valve and allows water into the system. Sprinkler heads discharge when the fire generates enough heat to activate one or more heads. Preaction systems are typically used in carousels containing high value product that is sensitive to accidental water discharge.
A clean agent system consists of one or more smoke detectors connected through a controller to a pressurized gas source and specially designed nozzles inside the carousel. When a fire is detected, the controller sounds an alarm, shuts the carousel door, disconnects power from the carousel and releases agent.